PS 180 (3 PHASE)---Raytech PS180 3 Phase Power Safe Management System Unit

specifications

Raytech PS180 3 Phase Power Safe Management System Unit

  • Detects & protects against following power Conditions:
  • Overvoltage
  • Undervoltage
  • Power Sags / Swells / Surges
  • Incorrect termination of 3 phase supplies (PS-180)
  • Neutral Failure
  • Under Frequency
  • Over Frequency

Monitoring :

  • Individual Phase True RMS Voltage Display
  • Individual Phase True RMS Current Display
  • Frequency Display
  • High Accuracy Measurements
  • Backlit LCD display for Setup Menu and Options
  • Earth-Neutral Voltage Monitoring. Verifies proper earthing, Neutral Displacement

Adjustable Protection Levels :

  • Over voltage 245-275 VAC
  • Under voltage 170-220 VAC with Disable
  • %-Over Frequency 50.5-55.0 hz with Disable
  • Under Frequency 45.5-49.5 hz with Disable

Features :

  • Bypass switch
  • Input Output via High current terminals / CEE norm connectos
  • Available with Distribution Options / MCB-s

*All specifications are subject to change without notice.